212 Connecting to Networks via RS-232/RS-485 Interface

Typical 3-Node Network

Modbus Communication
Protocol

Modbus is a Half-Duplex, master-slave communications protocol. The
Modbus network master reads and writes coils and registers. Modbus protocol
allows a single master to communicate with a maximum of 247 slave devices.
MicroLogix 1100 controllers support Modbus RTU Master and Modbus RTU
Slave protocol.

For more information on configuring your MicroLogix 1100 controller for
Modbus protocol, refer to the MicroLogix 1100 Programmable Controllers
Instruction Set Reference Manual, publication 1763-RM001. For more
information about the Modbus protocol, see the Modbus Protocol
Specifications (available from http://www.modbus.org).

ASCII

ASCII provides connection to other ASCII devices, such as bar code readers,
weigh scales, serial printers, and other intelligent devices.

You can use ASCII by configuring the RS-232/485 port, channel 0 for ASCII
driver. Refer to the MicroLogix 1100 Programmable Controllers Instruction
Set Reference Manual, publication 1763-RM001 for detailed configuration
information.

A-B

PanelView

TERM

A

B

COM

SHLD

CHS GND

TX

TX

PWR

TX

DC SOURCE

CABLE

EXTERNAL

PanelView 550

MicroLogix 1100

1761-CBL-AM00
or 1761-CBL-HM02

1747-CP3 or 1761-CBL-AC00

RJ45 port

1761-CBL-AS09
or 1761-CBL-AS03

AIC+

TIP

This 3-node network is not expandable.