Rockwell Automation 1763 MicroLogix 1100 Programmable Controllers User Manual User Manual

Page 168

Advertising
background image

Publication 1763-UM001D-EN-P - March 2011

166 Specifications

Output Specifications

Specification

1762-OA8

1762-OB8

1762-OB16

1762-OB32T

1762-OV32T

Shipping weight,
approx. (with carton)

215 g (0.48 lbs.)

210 g (0.46 lbs.)

235 g (0.52 lbs.)

200 g (0.44 lbs.)

200 g (0.44 lbs.)

Voltage category

100…240V AC

24V DC

24V DC

24V DC source

24V DC sink

Operating voltage
range

85…265V AC at
47…63 Hz

20.4…26.4V DC

20.4…26.4V DC

10.2…26.4V DC

10.2…26.4V DC

Number of outputs

8

8

16

32

32

Bus current draw, max.

115 mA at 5V DC
(0.575 W)

115 mA at 5V DC
(0.575 W)

175 mA at 5V DC
(0.88 W)

175 mA at 5V DC
0 mA at 24V DC

175 mA at 5V DC
0 mA at 24V DC

Heat dissipation, max.

2.9 W

1.61 W

2.9 W at 30 °C
(86 °F)
2.1 W at 55 °C
(131 °F)

3.4 W at 26.4 DC

2.7 W at 26.4V DC

Signal delay, max. –
resistive load

On delay: 1/2 cycle
Off delay: 1/2 cycle

On delay: 0.1 ms
Off delay: 1.0ms

On delay: 0.1 ms
Off delay: 1.0 ms

On delay: 0.5 ms
Off delay: 4.0 ms

On delay: 0.5 ms
Off delay: 4.0 ms

Off-state leakage
current, max.

2 mA at 132V,
2.5 mA at 265V

1.0 mA

1.0 mA

0.1 mA at 26.4V DC

0.1 mA at 26.4V DC

On-state current, min.

10 mA

1.0 mA

1.0 mA

1.0 mA

1.0 mA

On-state voltage drop,
max.

1.5V at 0.5 A

1.0V DC

1.0V DC

0.3V DC at 0.5 A

0.3V DC at 0.5A

Continuous current per
point, max.

0.25 A at 55 °C
(131 °F)
0.5 A at 30 °C
(86 °F)

0.5 A at 55 °C
(131 °F)
1.0 A at 30 °C
(86 °F)

0.5 A at 55 °C
(131 °F)
1.0 A at 30 °C
(86 °F)

0.5 A at 60 °C
(140 °F)

0.5A at 60 °C
(140 °F)

Continuous current per
common, max.

1.0 A at 55 °C
(131 °F)
2.0 A at 30 °C
(86 °F)

4.0 A at 55 °C
(131 °F)
8.0 A at 30 °C
(86 °F)

4.0 A at 55 °C
(131 °F)
8.0 A at 30 °C
(86 °F)

2.0 A at 60 °C
(140 °F)

2.0 A at 60 °C
(140 °F)

Continuous current per
module, max.

2.0 A at 55 °C
(131 °F)
4.0 A at 30 °C
(86 °F)

4.0 A at 55 °C;
8.0 A at 30 °C

4.0 A at 55 °C
(131 °F)

8.0 A at 30 °C
(86 °F)

4.0 A at 60 °C
(140 °F)

4.0 A at 60 °C
(140 °F)

Surge current, max.

5.0 A (Repeatability
is once every 2 s for
a duration of 25 ms.

2.0 A (Repeatability
is once every 2 s at
55 °C (131 °F), once
every second at
30 °C (86 °F) for a
duration of 10 ms.)

2.0 A (Repeatability
is once every 2 s at
55 °C (131 °F), once
every second at
30 °C (86 °F) for a
duration of 10 ms.)

2.0 A (Repeatability
is once every 2 s at
60 °C (140 °F) for
10 ms)

2.0 A (Repeatability
is once every 2 s at
60 °C (140 °F) for
10 ms)

Power supply distance
rating

6 (The module may not be more than 6 modules away from the power supply.)

Isolated groups

Group 1: Outputs 0
to 3

Group 2: Outputs 4
to 7

Group 1: Outputs 0
to 7

Group 1: Outputs 0
to 15

Group 1: Outputs 0…15

Group 2: Outputs 16…31 (internally
connected to common)