174 Specifications

Input Specifications 1762-IR4

Specification

1762-IR4

Input types

100

Ω

Platinum 385

200

Ω

Platinum 385

500

Ω

Platinum 385

1,000

Ω

Platinum 385

100

Ω

Platinum 3916

200

Ω

Platinum 3916

500

Ω

Platinum 3916

1,000

Ω

Platinum 3916

10

Ω

Copper 426

120

Ω

Nickel 672

120

Ω

Nickel 618

604

Ω

Nickel-Iron 518

0…150

Ω

0…500

Ω

0…1,000

Ω

0…3,000

Ω

Heat dissipation

1.5 Total Watts (The Watts per point, plus the minimum Watts, with all points enabled.)

Normal mode rejection ratio

70 dB minimum at 50 Hz with the 10 or 50 Hz filter selected
70 dB minimum at 60 Hz with the 10 or 60 Hz filter selected

Typical accuracy
[Autocalibration enabled] at 25 ° C (77 °F)
ambient with module operating
temperature at 25 °C (77 °F)

(1)

±0.5 °C (°F) for Pt 385
±0.4 °C (°F) for Pt 3916
±0.2 °C (°F) for Ni
±0.3 °C (°F) for NiFe
±0.6 °C (°F) for Cu

±0.15

Ω

for 150

Ω

range

±0.5

Ω

for 500

Ω

range

±1.0

Ω

for 1,000

Ω

range

±1.5

Ω

for 3,000

Ω

range

Typical accuracy
[Autocalibration enabled] at 0…55 °C
(32…131 °F)

(1)

±0.9 °C (°F) for Pt 385
±0.8 °C (°F) for Pt 3916
±0.4 °C (°F) for Ni
±0.5 °C (°F) for NiFe
±1.1 °C (°F) for Cu

±0.25

Ω

for 150

Ω

range

±0.8

Ω

for 500

Ω

range

±1.5

Ω

for 1,000

Ω

range

±2.5

Ω

for 3,000

Ω

range

Accuracy drift at 0…55 ° C (32…131 °F)

±0.026 °C/°C (0.026 °F/°F) for Pt 385
±0.023 °C/°C (0.023 °F/°F) for Pt
3916
±0.012 °C/°C (0.012 °F/°F) for Ni
±0.015 °C/°C (0.015 °F/°F) for NiFe
±0.032 °C/°C (0.032 °F/°F) for Cu

±0.007

Ω

/°C (0.012

Ω

/°F) for 150

Ω

range

±0.023

Ω

/°C (0.041

Ω

/°F) for 500

Ω

range

±0.043

Ω

/°C (0.077

Ω

/°F) for 1,000

Ω

range

±0.07 2

Ω

/°C (0.130

Ω

/°F) for 3,000

Ω

range

Excitation current source

0.5 mA and 1.0 mA selectable per channel

Open-circuit detection time

(2)

6…1212 ms

Input channel configuration

Via configuration software screen or the user program (by writing a unique bit pattern into the
module’s configuration file). Refer to your controller’s user manual to determine if user
program configuration is supported.

Calibration

The module performs autocalibration on channel enable and on a configuration change
between channels. You can also program the module to calibrate every five minutes.

Maximum overload at input terminals

±35V DC continuous