System loading example calculations – Rockwell Automation 1763 MicroLogix 1100 Programmable Controllers User Manual User Manual

Page 234

Advertising
background image

Publication 1763-UM001D-EN-P - March 2011

232 System Loading and Heat Dissipation

System Loading Example Calculations

Current Loading

Calculating the Current for Expansion I/O

Catalog Number

(1)

n

A

B

n x A

n x B

Number of
Modules

Device Current Requirements
(max)

Calculated Current

at 5V DC (mA)

at 24V DC (mA)

at 5V DC (mA)

at 24V DC (mA)

1762-IA8

2

50

0

100

0

1762-IF4

40

50

1762-IF2OF2

40

105

1762-IQ8

50

0

1762-IQ16

70

(2)

0

1762-IQ32T

170

0

1762-IR4

40

50

1762-IT4

40

50

1762-OA8

115

0

1762-OB8

115

0

1762-OB16

175

0

1762-OB32T

175

0

1762-OF4

40

165

1762-OV32T

175

0

1762-OW8

2

80

90

160

180

1762-OW16

140

(2)

180

(2)

1762-OX6I

110

110

1762-IQ8OW6

110

80

Total Modules (4 maximum):

4

Subtotal:

260

180

(1) Refer to your expansion I/O Installation Instructions for Current Requirements not listed in this table.

(2) Only applicable to Series B I/O modules.

Advertising