Connecting to a dh-485 network, Dh-485 configuration parameters – Rockwell Automation 1763 MicroLogix 1100 Programmable Controllers User Manual User Manual

Page 85

Advertising
background image

Publication 1763-UM001D-EN-P - March 2011

Communication Connections 83

Connecting to a DH-485
Network

The network diagrams on the next pages provide examples of how to connect
MicroLogix 1100 controllers to the DH-485 network.

You can connect a MicroLogix 1100 controller to your DH-485 network
directly without using an external optical isolator, such as Advanced Interface
Converter (AIC+), catalog number 1761-NET-AIC, as shown in the
illustrations below, because Channel 0 is isolated within the controller.

We recommend that you use a 1747-UIC USB interface to connect your PC to
a DH-485 network. For more information on the 1747-UIC, see the Universal
Serial Bus to DH-485 Interface Converter Installation Instructions
, publication
1747-IN063.

DH-485 Configuration Parameters

When MicroLogix communications are configured for DH-485, the following
parameters can be changed:

See

Software Considerations on page 208

for tips on setting the parameters

listed above.

TIP

Use a 1763-NC01 Series A or later (8-pin mini-DIN to
6-pin DH-485 connector) cable or equivalent to
connect a MicroLogix 1100 controller to a DH-485
network.

DF1 Full-Duplex Configuration Parameters

Parameter

Options

Baud Rate

9600, 19.2 KBps

Node Address

1...31 decimal

Token Hold Factor

1...4

A

TERM

B

COM

SHLD

CHS GND