Specifications 177

Thermocouple E (-270…-210 °C [-454…-346 °F])

±4.2 °C [±7.6 °F]

±6.3 °C [±11.4 °F]

±0.2698 °C/ °C [±0.2698 °F/ °F]

Thermocouple R

±1.7 °C [±3.1 °F]

±2.6 °C [±4.7 °F]

±0.0613 °C/ °C [±0.0613 °F/ °F]

Thermocouple S

±1.7 °C [±3.1 °F]

±2.6 °C [± 4.7 °F]

±0.0600 °C/ °C [±0.0600 °F/ °F]

Thermocouple C

±1.8 °C [±3.3 °F]

±3.5 °C [±6.3 °F]

±0.0899 °C/ °C [±0.0899 °F/ °F]

Thermocouple B

±3.0 °C [±5.4 °F]

±4.5 °C [±8.1 °F]

±0.1009 °C/ °C [±0.1009 °F/ °F]

±50 mV

±15

μ

V

±25

μ

V

±0.44

μ

V/ °C [±0.80

μ

V/ °F]

±100 mV

±20

μ

V

±30

μ

V

±0.69

μ

V/ °C [±01.25

μ

V/ °F]

(1) The module uses the National Institute of Standards and Technology (NIST) ITS-90 standard for thermocouple linearization.

(2) Accuracy and temperature drift information does not include the affects of errors or drift in the cold junction compensation circuit.

(3) Accuracy is dependent upon the analog/digital converter output rate selection, data format, and input noise.

(4) Temperature drift with autocalibration is slightly better than without autocalibration.

1762-IT4 Accuracy

Input Type

(1)

With Autocalibration Enabled

Without Autocalibration

Accuracy

(2)

(3)

for 10 Hz, 50 Hz and

60 Hz Filters (max.)

Maximum Temperature
Drift

(2)

(4)

at 25 °C [77 °F]
Ambient

at 0…60 °C
[32…140 °F]
Ambient

at 0…60 °C [32…140 °F]
Ambient

TIP

For more detailed 1762-IT4 accuracy information, see
publication 1762-UM002.

Output Specifications

Specification

1762-IF2OF2

1762-OF4

Number of outputs

2 single-ended (unipolar)

4 single-ended (unipolar)

(2)

Update time (typical)

4.5 ms

D/A converter type

Resistor string

R-2R Ladder Voltage Switching

Resistive load on current output

0…500

Ω

(includes wire resistance)

0…500

Ω

(includes wire resistance)

Load range on voltage output

> 1K

Ω

> 1K

Ω

Reactive load, current output

< 0.1 mH

< 0.1 mH

Reactive load, voltage output

< 1

μ

F

< 1

μ

F

Typical overall accuracy

(1)

±1.17% full scale at -20...65 °C

(2)

±0.5% full scale at 25 °C

±1.17% full scale at -20...65 °C

(2)

±0.5% full scale at 25 °C

Output ripple range 0…500 Hz
(referred to output range)

< ±0.1%

< ±0.1%