1762-IQ8OW6 Wiring Diagram

Analog Wiring

Consider the following when wiring your analog modules:

•

The analog common (COM) is not connected to earth ground inside the
module. All terminals are electrically isolated from the system.

•

Channels are not isolated from each other.

•

Use Belden 8761, or equivalent, shielded wire.

•

Under normal conditions, the drain wire (shield) should be connected to
the metal mounting panel (earth ground). Keep the shield connection to
earth ground as short as possible.

•

To ensure optimum accuracy for voltage type inputs, limit overall cable
impedance by keeping all analog cables as short as possible. Locate the
I/O system as close to your voltage type sensors or actuators as
possible.

•

The module does not provide loop power for analog inputs. Use a
power supply that matches the input transmitter specifications.