Analog modules – Rockwell Automation 1763 MicroLogix 1100 Programmable Controllers User Manual User Manual

Page 173

Advertising
background image

Publication 1763-UM001D-EN-P - March 2011

Specifications 171

Analog Modules

Common Specifications

Specification

1762-IF2OF2, 1762-IF4, 1762-IR4, 1762-IT4 and 1762-OF4

Dimensions

90 mm (height) x 87 mm (depth) x 40 mm (width)
height including mounting tabs is 110 mm

3.54 in. (height) x 3.43 in. (depth) x 1.58 in. (width)
height including mounting tabs is 4.33 in.

Temperature, storage

-40 °C…85 °C (-40 °F…185 °F)

Temperature, operating

-20 °C…65 °C (-4 °F…149 °F)

(1)

Operating humidity

5%…95% non-condensing

Operating altitude

2000 meters (6561 feet)

Vibration

Operating: 10…500 Hz, 5 g, 0.030 in. max. peak-to-peak

Shock

Operating: 30 g

Module power LED

On: indicates power is applied.

Recommended cable

Belden 8761 (shielded)
(For 1762-IT4, Shielded thermocouple extension wire for the specific type of thermocouple you are
using. Follow thermocouple manufacturer’s recommendations.)

Agency certification

C-UL certified (under CSA C22.2 No. 142)
UL 508 listed
CE compliant for all applicable directives
C-Tick marked for all applicable acts (1762-IR4 and 1762-IT4)

Hazardous environment class

Class I, Division 2, Hazardous Location, Groups A, B, C, D (UL 1604, C-UL under CSA C22.2 No. 213)

Noise immunity

NEMA standard ICS 2-230

Radiated and conducted emissions

EN50081-2 Class A

Electrical /EMC:

The module has passed testing at the following levels:

ESD immunity (IEC1000-4-2)

4 kV contact, 8 kV air, 4 kV indirect

Radiated immunity (IEC1000-4-3)

10 V/m, 80…1,000 MHz, 80% amplitude modulation, +900 MHz keyed carrier

Fast transient burst (IEC1000-4-4)

2 kV, 5 kHz

Surge immunity (IEC1000-4-5)

1 kV galvanic gun

Conducted immunity (IEC1000-4-6)

10V, 0.15…80 MHz

(2)

(3)

(1) For module-specific operating temperature range, refer to the Installation Instructions for the specific module.

(2) Conducted Immunity frequency range may be 150 kHz to 30 MHz if the Radiated Immunity frequency range is 30 MHz to 1000 MHz.

(3) For grounded thermocouples, the 10V level is reduced to 3V.