Dimensions

CENTERLINE 2500 MCCs are designed in widths between 600 and 1,000 mm.
Each column is 2300 mm high and either 600 mm or 800 mm deep. Double-front
columns are also available. See the column tables below for additional options.

Unit size is described in terms of modules. Each module is approximately 80 mm
high. Columns can accommodate 24 modules of varying unit combinations.

Figure 2 - Typical Column Dimensions

All measurements are in mm unless otherwise specified.

Table 2 - Column Width

Total Column Width

Unit Width

Vertical Wireway Width

600

(1)

(1) Only for full-column, frame mount applications.

600

No vertical wireway

700

500

200

800

300

900

400

1000

500

Table 3 - Column Depth

Single-front

Double-front

600

1200

800

1600 or 2000

(1)

(1) 800 mm columns can be mounted in a double-front

arrangement on site. A 400 mm air gap is required
between 3200 A and 4000 A double-front columns.

Table 4 - Column Height

Dimension

Measurement

Total Height

2300

Available Unit Height

1980

Top Horizontal Wireway

170

Bottom Horizontal Wireway

115

External Mounting Channel

35

170

1980

35

115

600…1000

600 or 800

2300

200…500

(1)

500 or 600

(1)

(1) Vertical wireway dimensions apply only to 500 mm wide units.