Door Latches, Operator Handles, and Unit Interlocks

Chapter 5

Locking Units in the OFF/O Position

Follow these procedures to lock a unit in the
OFF/O position.

1.

Turn the small rotary-operator handle to
the OFF/O position.

2.

Push and hold the button on the handle.
The lock opening is now visible.

3.

Insert and secure the lock.

Up to three 8 mm locks can be inserted.

Locking Units in the ON/I Position

Locking units in the ON/I position requires user modification. To modify the
operator handle to allow locking in the ON/I position, follow the procedure
illustrated in

Figure 18

.

Figure 18 - Modification of the Small Operator Handle to Allow Locking in the ON/I Position

ATTENTION: Follow all company safety and lockout procedures, and local codes
when performing this procedure.

ATTENTION: Locking an operating handle in the ON/

I position can conflict with

local codes and emergency shutdown requirements.

1

2

3

4

5

6

7

8

Click

Use screwdriver to
push down and
release lock.

Use screwdriver to
remove handle screw.