Door Latches, Operator Handles, and Unit Interlocks
Chapter 5
Closing the Unit Door
1.
Verify the large rotary-operator handle is in the OFF/O position.
2.
Slowly close the door until contact with the large rotary-operator handle is
made.
3.
Hold the large rotary-operator handle in the OFF/O position while
closing.
4.
Close the door and secure the door latches.
Opening the Unit Door in the ON/I Position
When the unit door is closed and the large rotary-operator handle is in the ON/I
position, a defeater mechanism must be deliberately operated to open the unit
door (for example, to open the door of an energized unit).
Follow these procedures to open a door
with the large rotary-operator handle in
the ON/I position.
1.
Release the door latches.
2.
Locate the defeater mechanism on
the right side of the handle.
3.
Use a flat blade screwdriver to
push the defeater mechanism in
the direction of the arrow.
4.
Carefully open the unit door.
ATTENTION: Follow local codes and guidelines, and the requirements of EN
50110 when working on energized equipment.
Defeater
Mechanism