Closing the unit door, Opening the unit door in the on/i position – Rockwell Automation 2500 CENTERLINE Motor Control Centers Installation Manual User Manual

Page 55

Advertising
background image

Rockwell Automation Publication 2500-IN001C-EN-P - April 2014

55

Door Latches, Operator Handles, and Unit Interlocks

Chapter 5

Closing the Unit Door

1.

Verify the large rotary-operator handle is in the OFF/O position.

2.

Slowly close the door until contact with the large rotary-operator handle is
made.

3.

Hold the large rotary-operator handle in the OFF/O position while
closing.

4.

Close the door and secure the door latches.

Opening the Unit Door in the ON/I Position

When the unit door is closed and the large rotary-operator handle is in the ON/I
position, a defeater mechanism must be deliberately operated to open the unit
door (for example, to open the door of an energized unit).

Follow these procedures to open a door
with the large rotary-operator handle in
the ON/I position.

1.

Release the door latches.

2.

Locate the defeater mechanism on
the right side of the handle.

3.

Use a flat blade screwdriver to
push the defeater mechanism in
the direction of the arrow.

4.

Carefully open the unit door.

ATTENTION: Follow local codes and guidelines, and the requirements of EN
50110 when working on energized equipment.

Defeater

Mechanism

Advertising