Selecting an Operating Position

1.

Grasp the withdraw lever with one hand.

2.

Slide the locking mechanism toward the withdraw lever.

3.

Rotate the withdraw lever to the desired position.

Mechanical detents are used to confirm that a position is selected.

4.

Release the locking mechanism and withdraw lever.

Connected Position

In the Connected position, the line, load, control, network, and PE connections
are engaged. Closing the unit door helps to keep the withdraw lever in the
connected position. To engage the interlock or turn the branch circuit device to
the ON/I position, the unit door must be fully closed.