Securing multiple-column shipping blocks – Rockwell Automation 2500 CENTERLINE Motor Control Centers Installation Manual User Manual

Page 34

Advertising
background image

34

Rockwell Automation Publication 2500-IN001C-EN-P - April 2014

Chapter 3

Install Columns

Securing Multiple-column Shipping Blocks

The following figures are for bolting down a multiple-column shipping block.
See

Figure 14 on page 36

for weld down requirements.

Figure 12 - Bolt-down Requirements for Single-front, Multiple-column-wide Shipping Blocks

IMPORTANT

Verify there is adequate clearance on the exposed sides of columns to access
the rear mounting bolt locations.

Use steel M12 bolts (minimum Property Class 8.8) to secure columns to the
foundation. Not all bolt locations are used.

Front

First Column

Last Column

Second Column

Installation sequence, left to right.

Installation sequence, right to left.

First Column

Last Column

Additional Columns

Second Column

Additional Column

Front

ATTENTION: The figure above shows which bolts are required for multiple-
column shipping blocks. Drawings with specific dimensions are supplied with
each multiple-column shipping block.

= Mounting hole locations not required.

Top View

Top View

Advertising