Securing multiple-column shipping blocks – Rockwell Automation 2500 CENTERLINE Motor Control Centers Installation Manual User Manual
Page 34

34
Rockwell Automation Publication 2500-IN001C-EN-P - April 2014
Chapter 3
Install Columns
Securing Multiple-column Shipping Blocks
The following figures are for bolting down a multiple-column shipping block.
See
for weld down requirements.
Figure 12 - Bolt-down Requirements for Single-front, Multiple-column-wide Shipping Blocks
IMPORTANT
Verify there is adequate clearance on the exposed sides of columns to access
the rear mounting bolt locations.
Use steel M12 bolts (minimum Property Class 8.8) to secure columns to the
foundation. Not all bolt locations are used.
Front
First Column
Last Column
Second Column
Installation sequence, left to right.
Installation sequence, right to left.
First Column
Last Column
Additional Columns
Second Column
Additional Column
Front
ATTENTION: The figure above shows which bolts are required for multiple-
column shipping blocks. Drawings with specific dimensions are supplied with
each multiple-column shipping block.
= Mounting hole locations not required.
Top View
Top View