Rockwell Automation Publication 2500-IN001C-EN-P - April 2014

75

Maintenance

Chapter 8

9. Coils

Check contactor and relay coils for signs of overheating

(cracking, melting or burnt insulation).
If signs of overheating are present, replace the coil.

Correct the overvoltage or undervoltage conditions that

caused coil failure.

Clean any residue of melted coil insulation from other parts

of the device or replace such parts.

10.Terminals

Check for loose wire connections and tighten as necessary.
Check schematics/component documentation for torque

values.
Power terminals
Control circuit terminals

Replace damaged parts or wiring.

11.Pilot Lights

Replace damaged lamps and lenses.

12.Fuses

Check fuses and fuse clips.

When replacing fuses, install the same type and rated

fuse that was originally furnished with the MCC.

13.Fans and Cooling

Devices

Inspect blowers and fans for operation and damage.

Replace blowers and fans that have bent, chipped or

missing blades, or if the shaft does not turn freely.

Clean or change air filters for fans.
Clean heat exchanger fins.

14.Solid State Devices

Perform a visual inspection. Components or circuit boards

must be replaced if the following are found:
Discoloration
Charred or burned components

Check printed circuit boards for:

Proper seating in the edge board connectors
Locking tabs in place

15.Unit Stabs

Inspect stabs for wear and/or corrosion. Replace if necessary.

If the line stab assembly is severely pitted, inspect the

vertical bus for wear and pitting. Replace as necessary.

Lightly lubricate line and load stabs with NO-OX-ID grease

before installing the unit into the column.

16.Control and

Network Plugs

Inspect for bent or damaged pins.

If necessary, clean the contacts.

Verify the connector mechanism is functioning properly.

17.Withdrawable Units

Remove dust and grease from the guide rail.
Check that the withdraw lever and locking mechanism

operate freely.

Check for easy movement of withdrawable units within the

column.

Test the unit interlock function.

18.Final Check

Verify all withdrawable units are in the correct operating

position (Connected, Test, Disconnected, Withdrawn).

Verify enclosure doors and wireway covers have been closed

and are secure.

After performing maintenance or repair, test the control

system for proper functioning under controlled conditions.

(1) The average temperature over a 24-hour period must not exceed 35 °C.

Suggested Maintenance Guidelines

Date

Remarks

Initials