Door Latches, Operator Handles, and Unit Interlocks

Opening the Unit Door in the ON/I Position

When the unit door is closed and the small rotary-operator handle is in the
ON/I or TRIPPED/T position, a defeater screw must be deliberately operated
to open the unit door.

1.

Release the door latches.

2.

Locate the defeater screw on the lower right corner of the small rotary-
operator handle.

3.

Use a flat blade (number 2) screwdriver to turn the defeater screw 10°
(maximum) clockwise.

4.

Carefully open the unit door.

Operator Handles for Circuit Breakers

In the event of a circuit breaker fault, the circuit breaker operator handle moves
to the TRIPPED/T position. Only reset the circuit breaker after the cause of the
fault has been determined and corrected.

Follow these procedures to reset the circuit breaker.

1.

Turn the small rotary-operator handle to the OFF/O position; see

Figure 17 on page 51

.

2.

After the fault has been corrected, verify that it is safe to re-energize the
unit and turn the small rotary-operator handle to the ON/I position.

ATTENTION: Follow local codes and guidelines in addition to the
requirements of EN 50110 when working on energized equipment.

Handle in ON/I Position

Handle in Tripped/T Position

10° maximum

turn clockwise.

Defeater Screw