Rockwell Automation Publication 2500-IN001C-EN-P - April 2014

35

Install Columns

Chapter 3

Figure 13 - Bolt-down Requirements for Double-front, Multiple-column-wide Shipping Blocks

IMPORTANT

Use steel M12 bolts (minimum Property Class 8.8) to secure columns to the
foundation. Not all bolt locations are used.

Front of Unit 1

Front of Unit 2

Installation sequence, left to right.

Installation sequence, right to left.

First Column

Last Column

Second Column

Additional Columns

First Column

Last Column

Second Column

Additional Columns

Front of Unit 1

Front of Unit 2

ATTENTION: The figure above shows which bolts are required for multiple-
column shipping blocks. Drawings with specific dimensions are supplied with
each multiple-column shipping block.

= Mounting hole locations not required.

Top View