Install Columns
Chapter 3
Figure 13 - Bolt-down Requirements for Double-front, Multiple-column-wide Shipping Blocks
IMPORTANT
Use steel M12 bolts (minimum Property Class 8.8) to secure columns to the
foundation. Not all bolt locations are used.
Front of Unit 1
Front of Unit 2
Installation sequence, left to right.
Installation sequence, right to left.
First Column
Last Column
Second Column
Additional Columns
First Column
Last Column
Second Column
Additional Columns
Front of Unit 1
Front of Unit 2
ATTENTION: The figure above shows which bolts are required for multiple-
column shipping blocks. Drawings with specific dimensions are supplied with
each multiple-column shipping block.
= Mounting hole locations not required.
Top View
Top View