Ethernet/ip software installation checklist, Devicenet motor control centers, Preparing a devicenet system for commission – Rockwell Automation 2500 CENTERLINE Motor Control Centers Installation Manual User Manual

Page 83

Advertising
background image

Rockwell Automation Publication 2500-IN001C-EN-P - April 2014

83

IntelliCENTER Options

Chapter 9

EtherNet/IP Software Installation Checklist

The following steps, along with references for more information, are provided to
assist with the EtherNet/IP software installation process.

1.

Install the communication card in your personal computer.

2.

Load the Windows hardware drivers for the communication card.

3.

Load RSLinx® software.

4.

Configure the RSLinx driver.

Within the RSWho function, make sure no unrecognized devices (the ‘?’
symbols) appear for any devices. If an unrecognized device appears, load
the electronic data sheet (EDS) file.

Refer to the

Electronic Data Sheets (EDS)

section below for additional

details.

5.

Use the device web pages or RSLogix™ 5000 software to program and
configure devices (for example, full load current, acceleration rate).

6.

Write the PLC program.

7.

If IntelliCENTER software is provided, load per the IntelliCENTER
Software User Guide, publication

MCC-UM001

.

DeviceNet Motor Control
Centers

This section explains how to connect the terminating resistors and join the
DeviceNet cables.

Preparing a DeviceNet System for Commission

If your CENTERLINE 2500 MCC is equipped with DeviceNet, terminating
resistors must be installed prior to commissioning. If your MCC consists of more
than one shipping block, DeviceNet splicing cables need to be installed as
columns are joined together.

Basic information is provided in the following sections. For additional
information, refer to DeviceNet Motor Control Centers (MCCs), publication

2500-TD002

.

IMPORTANT

Do not leave the RSWho constantly browsing. Close the RSWho screen
or disable Autobrowse.