Rockwell Automation Publication 2500-IN001C-EN-P - April 2014

59

Chapter

6

Install and Remove Units

Unit Size

Unit size is described in terms of modules. One module is 80 mm high by 500
mm wide. Withdrawable units are available is the following sizes: 1, 2, 4, 6, 8, 10,
and 12 modules. Fixed units range in size from 4…24 modules.

Any unit size above one module must be in even increments. Therefore, you
cannot have a unit that is 11 modules high.

CENTERLINE 2500 MCCs are available with many combinations of
withdrawable and fixed units. This table lists the maximum ampere rating of each
unit size.

Figure 21 - Unit Types

Number of Modules

Ampere Rating (max)

1

32 A

2…12

225 A

One Module Unit

Four Module Unit