Rockwell Automation Publication 2500-IN001C-EN-P - April 2014

29

Install Columns

Chapter 3

Securing a Motor Control
Center

Documentation packages shipped with assembled MCCs include an MCC
elevation drawing showing an MCC floor plan layout. To secure a column to the
foundation, refer to the provided floor plan layout and the following procedures.

Refer to

Chapter 4

for cable and conduit routing instructions.

Securing Methods

MCC columns or shipping blocks can be bolted or welded to a foundation. Two
mounting channels on the bottom of each MCC column are used for either
securing method.

Weld Down Method

See

Figure 13 on page 35

for welding a MCC column or shipping block to a

foundation.

Bolt Down Method

The two mounting channels allow up to four steel M12 bolts (minimum
Property Class 8.8) for each MCC column. We recommend that these bolts be
pre-located and embedded in the foundation before installing each MCC
column. See

page 31

through

page 33

for mounting bolt locations.

Figure 11 - Mounting Channel Dimensions and Bolt Locations

All dimensions are mm.

MCC Column Width

A

B

600

597

461

700

697

561

800

797

661

900

897

761

1000

997

861

TIP

Mounting channel is not flush with the sides of the MCC column.

A

B

38

68

Mounting holes (2)
18 mm dia.