Technical data – Rockwell Automation 2500 CENTERLINE Motor Control Centers Installation Manual User Manual

Page 17

Advertising
background image

Rockwell Automation Publication 2500-IN001C-EN-P - April 2014

17

System Overview

Chapter 1

Technical Data

This table provides the technical specifications for the 2500 MCC.

Standards

EN 60204-1:2006

Safety of machinery – electrical equipment of machines; Part 1: General requirements

IEC 61439-1 Ed. 2.0 b:2011

Low-voltage switchgear and controlgear assemblies; Part 1: General rules

EC Directives

IEC/TR 61641, ed. 2.0 2008-1

Enclosed low-voltage switchgear and controlgear assemblies – guide for testing under conditions of arcing due
to internal fault

2004/108/EC

EMC directive

2006/95/EEC

Low voltage directive

Certifications and
Markings

ABS
ABS Shipboard

http://www.rockwellautomation.com/rockwellautomation/certification/marine.page?

C-Tick

http://www.rockwellautomation.com/rockwellautomation/certification/c-tick.page?

CE Conformance Marked

http://www.rockwellautomation.com/rockwellautomation/certification/ce/page?#Motor

China Compulsory Certificate (CCC)

http://www.rockwellautomation.com/rockwellautomation/certification/china.page?#motorcontrol

DEKRA

http://www.rockwellautomation.com/rockwellautomation/certification/third.page?

GOST-R

http://www.rockwellautomation.com/rockwellautomation/certification/gost/page?#/tab1

IBC 2010

http://www.rockwellautomation.com/rockwellautomation/certification/overview.page?

ICC–ES AC156

http://www.rockwellautomation.com/rockwellautomation/certification/overview.page?

IEEE 344

http://www.rockwellautomation.com/rockwellautomation/certification/overview.page?

KEMA

http://www.rockwellautomation.com/rockwellautomation/certification/third.page?

SEI/ASCE 7-05 and 7-10

http://www.rockwellautomation.com/rockwellautomation/certification/overview.page?

Rated Voltages

Rated operating voltage, U

e

Up to 690V, 3-phase

Rated frequency, f

n

50…60 Hz

Rated insulation voltage, U

i

1000V, 3-phase

Rated Currents

Continuous current rating, I

e

Horizontal bus - up to 4000 A

Vertical bus - up to 1200 A per column

(3)

Short circuit peak withstand, I

pk

Horizontal and vertical buses - up to 210 kA

Short time withstand rating, I

cw

Horizontal and vertical buses - up to 100 kA for 1 second

Neutral (N)

Full or half-rated

Creepage Distances
and Clearances

Rated impulse withstand voltage, U

imp

6, 8, or 12 kV

Material group (overvoltage category)

IIIa (175 </= CTI < 400)

Pollution degree

3

Bus Material and
Plating

Horizontal power bus

Copper (optional tin plating)

Vertical distribution bus

Copper with tin plating

Protective earth conductor (PE)

Copper (optional tin plating)

Degrees of
Protection

IEC 60529

IP20, IP42, or IP54

Forms of Separation

IEC 61439-1

Form 2b, 3b, or 4b

Column Dimensions

Height

See

page 14

Width

Depth

Units

Module size

80 mm high x 500 mm wide = 1 module

Modules per column, max

24 (23 for high density)

Withdrawable unit sizes

1, 2, 4, 6, 8, 10, 12 modules

Structural Surface
Treatments

Interior

G90 galvanized metal

(1)

Exterior

RAL 7032 Pebble Grey paint or Munsell 6.5 paint (additional colors available by request)

Environment

Storage temperature

-25…55 °C

Operating (ambient) temperature

-5…40 °C

(2)

with up to 95% non-condensing humidity

Altitude

Up to 1000 m without derating: derated after 1000 m

(1) Interior painted surfaces available as custom paint requests.
(2) The average temperature over a 24-hour period must not exceed 35 °C.
(3) Up to 600 A top and bottom, effective 1200 A per column.