Chapter 6 Configuring FactoryTalk Historian


102

Rockwell Automation Publication HSE-IN024A-EN-E–December 2012

As a general rule, you must always disable buffering on the
interface before you delete it. If you forget to disable buffering,
you will have to restart the computer to make sure the
buffering subsystem is restarted.

12. Select Buffered Servers in the left pane of the dialog box.

From the Buffering to collective/server drop-down list,

select the name of the computer on which the FactoryTalk
Historian Live Data Interface is installed, and click Yes in to
the confirmation message box.

13. Click OK to close the Buffering dialog box.
14. From the tree in the Interface Configuration Utility dialog

box, select Service.

15. In the Dependencies box, add the pibufss service from the

Installed services list.

NOTE

Add pibufss as a dependent service to make sure your interface

always starts after the buffering service starts.

IMPORTANT

If the interface starts before the buffering subsystem, data will
be lost.

16. On the toolbar, click to restart the interface.
17. Verify that the status bar at the bottom of the dialog box

displays the status Ready and Running.

18. Click Close to exit the Interface Configuration Utility

dialog box. The buffering service is now configured.