Appendix A Configuring Historian Servers in High Availability Mode


124

Rockwell Automation Publication HSE-IN024A-EN-E–December 2012

To verify that a Historian server collective replicates primary server
configuration changes to all secondary servers, you can edit a point
on the primary server and verify the change on the secondary server
in the collective.

To verify configuration replication in a Historian server
collective:

1. Click

Start > All Programs > Rockwell Software > FactoryTalk

Historian SE > System Management Tools. The System
Management Tools
dialog box appears.

2. Under Collectives and Servers, select all the servers that are

members in the collective.

3. Under System Management Tools, select Points > Point

Builder.

4. Add a point found in all the servers to the list of points:

1. On the toolbar, click

. The Tag Search dialog box

appears.

2. In Tag Mask, type

sinusoid.

3. Click Search to find all instances of this built-in point on

the selected servers.

4. Click Select All to choose all instances.
5. Click OK to add these points to the list of points in the

Point Builder.

5. Edit the point on the primary server:

1. Select the point on the primary server.

The Point Builder shows the configuration of the selected
point in the tabs at the bottom of the System Management
Tools
dialog box.

Verifying Replication of
Configuration Changes in
the Primary Server