Chapter 7 Troubleshooting FactoryTalk Historian


112

Rockwell Automation Publication HSE-IN024A-EN-E–December 2012

Message

Due to the lack of connection to the network, some of the
FactoryTalk Historian components have not been correctly
configured.

Cause

The warning occurs if you try to create the schema in the
FactoryTalk Directory when your client computer is not connected

to the network.

Resolution

Manually create a connection to the FactoryTalk Directory and add
the schema information. See the instruction below.

To add the schema information to the FactoryTalk Directory, we
recommend that you execute the FTHMESecurityUpdate.bat file.
It is located in the Redist\FTHME Security directory on your

FactoryTalk Historian SE installation DVD. The file automatically
adds schema information and folders to the FactoryTalk Directory
on your client computer.

To manually add the schema information to the FactoryTalk
Directory:

Open the Command Prompt window and type the following:

"[ProgramFilesFolder]Rockwell Software\Management
Tools\FTHistorianInstallSetup.exe"
"[CommonAppDataFolder]Rockwell Automation\FactoryTalk
Historian\FTHistorianSchema.xml"
"[CommonAppDataFolder]Rockwell Automation\FactoryTalk

Historian\FTHistorianStrings.xml" -G

, where:

[ProgramFilesFolder] is the system's Program Files (x86)

directory (e.g.

C:\Program Files (x86))

[CommonAppDataFolder] is the system's ProgramData

directory (e.g.

C:\ProgramData)

Schema Creation