Chapter 7

Troubleshooting FactoryTalk Historian

In this chapter you will learn how to:

• Use FactoryTalk Historian ME modules with FactoryTalk

Security (page 107).

• Verify the Windows Administrator privileges (page 108).
• Resolve error and warning messages (page 109).

If you are using FactoryTalk Security to authenticate your
FactoryTalk Historian ME 1756-HISTxG module, and you want to
establish a connection between the Historian ME and SE modules,
you need to make sure the following FactoryTalk Security groups are
created in FactoryTalk Historian SE:

• FTHAdministrators
• FTHEngineers
• FTHSupervisors
• FTHOperators

To verify that these four user groups were created:

1. Click

Start > All Programs > Rockwell Software > FactoryTalk

Administration Console. The FactoryTalk Administration
Console
dialog box appears.

2. In the Select FactoryTalk Directory dialog box, select

Network, and click OK.

3. In the Explorer tree, expand Users and Groups > User

Groups.