Chapter 7 Troubleshooting FactoryTalk Historian


114

Rockwell Automation Publication HSE-IN024A-EN-E–December 2012

During the installation, the FactoryTalk Historian suites attempt to
update the configuration of the system firewall using the Rockwell
Firewall Configuration Utility (WFCU) that has been installed
along with FactoryTalk Services Platform.

If the update of the firewall configuration cannot be completed
during the installation, a relevant error message is displayed on the
last page of the FactoryTalk Historian installation wizard.

The errors fall into the following categories, depending on the
firewall configuration you have:

• The errors that may appear if you use Windows Firewall to

configure network security on the computer with FactoryTalk
Historian installed:

Error number

Description

20

The user has insufficient permissions to modify Windows

Firewall rules.

200

The user has declined to make the changes to the
configuration of Windows Firewall.

320

The network connection specified in WFCU could not be
found.
Cause: No network connection is configured.
Resolution: Configure the network connection and then
configure Windows Firewall.

See "Configuring Windows Firewall with WFCU (page 115)"
for details.

• The errors that may appear if you use another firewall utility to

configure network security on the computer with FactoryTalk
Historian installed:

Error number

Description

10

The version of Windows Firewall is not supported by WFCU.

100

Some parameters of the WFCU configuration are missing.

110

Some parameters of the WFCU configuration are incorrect.

Firewall-related Errors