Chapter 6 Configuring FactoryTalk Historian


98

Rockwell Automation Publication HSE-IN024A-EN-E–December 2012

The interface collects data points (tags) from the data server and
passes them to the FactoryTalk Historian SE server. Install the
FactoryTalk Historian Live Data Interface component on the same
computer as the data server. After installing the interface, configure

the buffering service on the data server computer. The buffering
service stores data in its memory so that in the event the interface is
not able to communicate with the FactoryTalk Historian SE server,
the data will not be lost.

When you create a Historian server connection in the FactoryTalk
Administration Console (page 75), a default Live Data Interface
instance

FTLD1 is created and registered.

To register another instance of the FactoryTalk Historian Live
Data Interface:

1. On the computer with the FactoryTalk Historian SE server

installed, go to

Start > All Programs > Rockwell Software >

FactoryTalk Administration Console.

2. In the Select FactoryTalk Directory dialog box, click

Network.

3. In the Explorer tree of the FactoryTalk Administration

Console dialog box, go to System > Connections >
Historical Data
, right-click the FactoryTalk Historian server
connection name, and select New Data Collection Interface.
The Data Collection Interface Properties dialog box

appears.

4. In the Computer hosting the interface drop-down list, select

the name of the computer on which you have installed the data
server and the FactoryTalk Historian Live Data Interface.

5. From the Startup Type drop-down list, choose Automatic.
6. Click Apply.

Configuring FactoryTalk
Historian Live Data
Interface

Registering Live Data
Interfaces