Construct Your Starter Kit 2-15

Ground Your Network

You only need to ground a flat media DeviceNet network at one
location. Follow the guidelines below:

Ground the V- conductor at one place.

Make this ground connection with a 25 mm (1 in.) copper braid
or a #8 AWG wire up to a maximum 3m (10 ft) in length.

Use the same ground for the V- conductor of the cable system
and the chassis ground of the power supply. Do this at the
power supply.

Set up the 1771-SDN
Scanner for SKITs 3 and 4

The scanner is the DeviceNet master (controller interface)
coordinating all control data to and from all devices on the DeviceNet
network. This DeviceNet data is transferred between:

the SLC-500 and 1747-SDN via M1/M0 and discrete I/O transfers

PLC-5 and 1771-SDN via block transfers and discrete I/O
transfers

PCIDS and logic engine (such as SoftLogix 5 or your own
application) via I/O Linx driver running in the NT kernel

This data is then used in the ladder logic program to do the actual
control logic.

Wire
Color

Wire
Identity

Usage

white

CAN_H

signal

blue

CAN_L

signal

black

V-

power

red

V+

power

Flat media

CAN_H

CAN_L

V-

V-

V+

V+