2-16 Construct Your Starter Kit

Set Node Address Switches for Channel 1

You must set the node address for the 1771-SDN before you install the
scanner and go online. To set the I/O chassis addressing node
switches:

1. Locate the switch bank labeled “Channel 1” on the left side of

the module.

The address range is from 0 to 63. It will be set to 63 from the
factory as shown in the illustration. All autobaud devices are
internally set to node 63. The node address for DeviceNet
Channel 1 must not conflict with the node address of any other
device on the network. For this demonstration, you want to set
the address to 0.

2. Use a ball point pen or a similar object to adjust switches 3

through 8 to match the illustration. All of the switches should be
in the off, in the 0 position.

Install Your Scanner

After you set the dip switches and with the chassis power off, insert
the 1771-SDN scanner into slot 2 of your PLC-5 processor chassis.

IMPORTANT

Do not use a lead pencil because the tip can break
off and jam or short out the switch.

Channel 1 DIP switches

On=1

Off=0

On=1

Off=0

8

set
from
factory

Node 63

on

1 2 3 4 5

6 7 8

Node 0

set for
SKITs
3 & 4

on

1 2 3 4 5

6 7 8

30292

IMPORTANT

Be certain to turn the power to your chassis off
before inserting your scanner.

IMPORTANT

Refer to installation instructions that come with your
1771-SDN for installation details.