OPERATOR’S MANUAL

IntelliAg MVT

11001-1643-201401

TROUBLESHOOTING & ALARM CODES / 107

215

High Pressure Limit
Exceeded Alarm

SENSED PRESSURE EXCEEDS THE
HIGH ALARM SETTING ON THE
PRESSURE SETUP SCREEN.
1. Implement malfunction or incorrect
setup.
2. Defective pressure sensor.
3. Defective module.

1. Verify proper implement operation/setup.
2. Inspect pressure sensor for damage.
Replace if necessary.
3. Inspect module for damage. Replace if
necessary.

216

Low Pressure Limit
Exceeded Alarm

SENSED PRESSURE BELOW THE LOW
ALARM SETTING ON THE PRESSURE
SETUP SCREEN.
1. Implement malfunction or incorrect setup.
2. Defective pressure sensor.
3. Defective module harness or module.

1. Verify proper implement operation/setup.
2. Inspect pressure sensor for damage.
Replace if necessary.
3. Inspect module and/or module harness for
damage. Replace if necessary.

217

Member Module
Detection Alarm

NUMBER OF MEMBER MODULES DOES
NOT MATCH THE SYSTEM
CONFIGURATION.
1. Too few modules connect to system.
2. Too many modules connected to
system.
3. Defective CAN/module harness.
4. Blown module harness fuse.
5. Defective module.
6. New module has been added to system.

1. Verify correct module configuration setup
on the Module Configuration screen.
2. Verify correct module configuration setup
on the Module Configuration screen.
3. Identify missing module in the Module
Configuration list. Inspect CAN/module
harness of the missing module for damage.
Repair or replace harness.
4. Inspect module harness fuse of the
identified module. Replace if necessary.
5. Identify missing module in the Module
Configuration list. Inspect missing module
for damage or replace.
6. Verify correct module configuration setup
on the Module Configuration screen.

218

Pressure Sensor
Detection Alarm

NUMBER OF PRESSURE SENSORS
CONNECTED DOES NOT AGREE WITH
THE NUMBER OF SENSORS
CONFIGURED ON THE PRESSURE
SENSOR CONFIGURATION SCREEN.
1. Defective Sensor.
2. Defective module or damaged module
harness.
3. Additional pressure sensor detected.

1. Inspect pressure sensor for damage or
replace.
2. Inspect module and/or module harness
for damage. Replace if necessary.
3. Verify correct# ACC setting for each
module.

219

Row Sensor Detection
Alarm

NUMBER OF SEED SENSORS
CONNECTED DOES NOT AGREE WITH
THE NUMBER OF SENSORS
CONFIGURED ON THE SEED SENSOR
CONFIGURATION SCREEN.
1. Defective seed sensor.
2. Defective module or damaged module
harness.
3. Additional seed sensor detected.

1. Inspect seed sensor for damage or
replace.
2. Inspect module and/or module harness
for damage. Replace if necessary.
3. Verify correct # ROWS setting for each
module.

220

Row Sensors Installed
Incorrectly Alarm

ROWS ARE NOT DETECTED
SEQUENTIALLY ON A MODULE.
1. Incorrect seed row connections.
2. Defective seed sensor.
3. Defective module or damaged module
harness.

1. Verify seed sensors are connected
sequentially on all modules as instructed in
installation.
2. Inspect seed sensor for damage or
replace.
3. Inspect module and/or module harness
for damage. Replace if necessary.

221

Channel Invalid State
Alarm

1. Internal system software error.

1. Cycle system power Off/On. If condition
persists, contact DICKEY-john Technical
Support (1-800-637-3302) or DICKEY-john
Europe (011-22-141-192180).

ALARM
#

ALARM

PROBABLE CAUSE

CORRECTIVE ACTION