BPS / MX / RS Series SCPI Programming Manual

AMETEK Programmable Power

Manual P/N 7003-961 Rev. AA

105

Parameter Set

Action

DCYCle

PERiod

WIDTh

Sets WIDTh. If WIDTh < PERiod, recalculates DCYCle;
otherwise, recalculates the PERiod and DCYCle.

Sets PERiod. If WIDTh < PERiod, recalculates DCYCle;
otherwise, recalculates the PERiod and DCYCle.

Sets DCYCle and recalculates PERiod

Table 4-1 : PULSe:HOLD = WIDTh parameters

Parameter Set

Action

DCYCle

PERiod

WIDTh

Sets WIDTh and recalculates the PERiod

Sets PERiod and recalculates the WIDTh

Sets DCYCle and recalculates PERiod

Table 4-2 : PULSe:HOLD = DCYCle parameters

PULSe:DCYCle

This command sets the duty cycle of the triggered output pulse. The duty cycle units are
specified in percent.

Command Syntax

[SOURce:]PULSe:DCYCle<NRf+>

Parameters

0 to 100%|MINimum|MAXimum

*RST Value

50%

Examples PULS:DCYC

75

PULS:DCYC

MAX

Query Syntax

[SOURce:]PULSe:DCYCle?

Returned Parameters

<NR2>

Related Commands

PULS:COUN

PULS:PER

PULS:WIDT

PULSe:PERiod

This command sets the period of a triggered output transient The command parameters are
model-dependent.

Command Syntax

[SOURce:]PULSe:PERiod<NRf+>

Parameters

2 msecs to 90,000 secs|MINimum|MAXimum

Unit S

(seconds)

*RST Value

1 sec

Examples

PER 0.001PER MIN

Query Syntax

[SOURce:]PERiod?

Returned Parameters

<NR2>

Related Commands

PULS:COUN

PULS:DCYC

PULS:WIDT