RLE FMS V.1.13 User Manual

Page 102

Advertising
background image

102

FMS User Guide

800.518.1519

3

Web Interface Configuration

Serial Com 1

Protocol Type

Configures the Serial COM Port 1 (EIA-232 or EIA-485). Available

options are:

Modbus Master: Enables the FMS to operate as a Modbus

Master over Serial COM1.

Modbus Slave: Enables the FMS to operate as a Modbus

Slave over Serial COM1.

Telnet: Enables the FMS to communicate via Serial COM Port

1.

SMS/Text: Enables the FMS to communicate to a SMS modem

via Serial COM1.

Master Protocol

Type

Configures the FMS Master Protocol type to be used, via Serial or

TCP/IP. Select one of the following options:

None: Disables Modbus support.

Modbus/SNMP/BACnet Master - 32 Units: This is the most

typical configuration for the FMS. Select this option when there

is at least one Slave unit. This option can be configured to poll

data from up to 32 Slave devices.

Modbus Master BCM H663 - 4 Units: Select this option when

there are 1 to 4 BCMs (Branch Circuit Monitors) and no other

Slave devices. This option enables web pages that are unique

to the BCM allowing for easier setup. SNMP (Get, Set and

Traps) is supported for the BCMs.

Modbus Master BCM H663 - 16 Units: Select this option when

there are 5 to 16 BCMs (Branch Circuit Monitors) and no other

Slave devices. This option enables web pages that are unique

to the BCM allowing for easier setup. SNMP (Get, Set and

Traps) is not supported for the BCMs. SNMP is still supported

for the local I/O (Inputs 1 - 104). If SNMP is required for the

BCMs, additional FMSs are required to allow a maximum of 4

BCMs per FMS.

Serial Baud Rate

This option sets the Serial COM Port 1 to 1200, 2400 or 9600 Baud.

All the devices connected to the FMS Serial COM Port 1 must be

set to operate at the same Baud rate.

Serial Interface Type Enable the FMS Modbus to operate on the EIA-485 or EIA-232

COM Port 1.

Telnet Inactivity

Timeout

After this many minutes of inactivity, the FMS will timeout of Telnet

communication.

Modbus Serial Slave

Address

This option sets the FMS Modbus Slave address for the Serial

COM Port 1 - this field is required when the Serial Protocol is set to

“Modbus Slave.”
Each Slave device on the Modbus network must have a unique

address.

Master Poll Timeout

This is the amount of time the FMS waits for a response from the

Slave device before moving on to read the next register. It is

adjustable from 1 to 10 seconds.
The timeout is active only when the Serial Protocol is set to

“Modbus Master Generic - 32 Units,” “Modbus Master BCM H663 -

4 Units” or “Modbus Master BCM H663 - 16 Units.”

Default: 1 second

Option

Description

Table 3.27

Modbus/SNMP/BACnet/Telnet Master Options