RLE FMS V.1.13 User Manual

Page 48

Advertising
background image

48

FMS User Guide

800.518.1519

3

Web Interface Configuration

Hysteresis

Applies when the input type is Analog 4-20mA and is active for High

Limit 1, High Limit 2, Low Limit 1 and Low Limit 2.

Hysteresis (also referred to as deadband) designates the amount

an input reading must sway from its preset alarm reading before it

is classified as returned to normal. It effectively provides a

deadband around the limit settings, which prevents sensors from

sending multiple alarm and return to normal alerts when the

sensor’s value hovers around its alarm limit.

Example: A temperature sensor alarms when it reaches its High

Limit 1 of 80°F. If Hysteresis is set at two, the sensor must register

less than 78°F before the FMS reports it as returned to normal.
In another example, a humidity sensor alarms when it reaches its

Low Limit 2 of 30% RH. If the Hysteresis is set at five, the humidity

must register more than 35% before the FMS reports it as returned

to normal.

UOM/Map Label

The 10 character field used to assign a unit of measure label to

analog values, such as °F, °C, % RH, Amps, Volts, PSI, etc. The

unit of measure field is only required when the input type is Analog

4-20mA. The unit of measure field is displayed on the Main Menu

and in notification (email/pager messages and SNMP Trap).

Alarm Delay

The amount of time the FMS waits to send an alert after an alarm

condition is detected. The FMS uses this same time delay to report

a return to normal after the alarm condition clears. The alarm delay

is active for all input types except Not Configured.

Example: An CRAC unit input is configured with an alarm delay of

10 seconds. If the CRAC unit goes into alarm and then returns to

normal within10 seconds, no alarm is generated in the FMS.
If the CRAC unit remains in alarm for 10 seconds or more, the FMS

records the alarm and generates notification per the input settings.
If the CRAC unit returns to normal but then alarms again within 10

seconds, the FMS does not record this as a return to normal. Once

the CRAC unit returns to normal for greater than 10 seconds, the

FMS records a return to normal and generates its notifications.

High Limit2 (Major)

Applies only to analog 4-20mA inputs.

The FMS will record an alarm and send notification when the FMS

calculated value exceeds this limit. The High Limit 1 and High Limit

2 are disabled when they are both set to 0. High Limit 2 will also

activate any designated relays.

High Limit1 (Minor)

Applies only to analog 4-20mA inputs.

The FMS will record an alarm and send notification when the FMS

calculated value exceeds this limit. The High Limit 1 and High Limit

2 are disabled when they are both set to 0.

Option

Description

Table 3.3

FMS Main Board Configuration Options

Advertising