3.5. History

The History link provides access to a wide variety of logged historical data for the FMS.

3.5.1 Alarm History

Alarm History displays the last 256 alarms captured by the FMS. Alarms are ranked from

most recent (top of the list) to least recent (bottom of the list).

Figure 3.66

Alarm History Page

The following format is used to record each alarm entry:

Date Time AH###-ID-Condition Severity (Value UOM) Label

Date and Time is the internal date and time stamp of the alarm condition.

AH### is the alarm entry index.

ID is the alarm identifier number; see

Appendix E, “Alarm ID Reference Tables” on

page 199

.

Condition is On, High1, High2, Low1, Low2, or RTN (Returned to Normal).

Severity is Critical, Major, Major*Hi, Minor, Minor*Hi, Warning, or Clear

Label is the alarm descriptor, up to 64 characters long.

Value and Unit of Measure (UOM) is captured for analog channels only. The value

recorded is the actual analog value that exceeded its alarm threshold.

The Alarm History log entries are color-coded as follows:

Color

Description

Red

A point configured for dial out (pager) is in alarm and is unacknowledged. The

alarm will be red if the point is configured for both pager and email notification.

Orange

A point not configured for dial out (pager) is in alarm and is unacknowledged.

Blue

The alarm has been acknowledged.

Black

The alarm has returned to normal.

Table 3.31

Alarm History Log Entries