Web Interface Configuration

3.4.1.3 Expansion Card “C” Input Configuration

Expansion Card C contains 24 digital NO/NC inputs.

While units will vary depending on individual configurations, Expansion Card C is typically

numbered 1.1-1.24, 2.1-2.24, etc.

This page will be displayed when configuring inputs for Expansion Card C. It is similar to the

FMS Main Board Input Configuration page – see

3.4.1.1, “Main Card - Input Channels 1-8”

on page 45

—with the following exceptions:

The Input Type options do not include Analog 4-20mA since Expansion Card “C” only

accepts dry contact inputs.

The Gain, Offset, Hysteresis, Unit of Measure, High Limit 2, High Limit 1, Low Limit 1,

and Low Limit 2 are not available since Expansion Card “C” does not accept analog inputs.

The option for Individual Ground Type (digital input only) is removed. Expansion Card

“C” accepts Individual and Common Ground inputs; however, it does not require any

software configuration.

Figure 3.9

Expansion Card “C” Configuration Page

3.4.1.4 Internal Temperature and Internal Humidity Configuration

Internal temperature and humidity sensors are optional, and are not included on all FMS

configurations. Internal Temperature, Ch. 105, and Internal Humidity, Ch. 106, have the same

options as a standard channel configured as an analog input, but the gain value cannot be

changed-it has a fixed value internally. The Input Type for Internal Temperature is used to

specify and display the input in Fahrenheit or Celsius.