RLE FMS V.1.13 User Manual

Page 47

Advertising
background image

rletech.com

FMS User Guide

47

3

Web Interface Configuration

Gain & Offset

Inputs like temperature, humidity, pressure, etc. connected to the

FMS convert information to a 4-20mA signal. The FMS reads this

raw 4-20mA signal and calculates a value based on the input and

the predetermined gain and offset settings. The idea is to determine

the correct gain and offset values so that the FMS calculates and

displays an accurate reading. Without setting the correct gain and

offset, the FMS will not convert the raw data correctly. As a result,

missed alarms or nuisance alarms could occur.
To set gain and offset values, click the Calculator link.

Enter the sensor’s range and press the Calculate button. Click the

Return to Input 1 Configuration link so that the gain and offset

fields are automatically entered with the correct offset and gain

settings. Gain and offset values can also be determined by using

the following formulas:

Gain for 4-20mA Transducer = (Sensor High Range Value-

Sensor Low Range Value) / 4

Offset for 4-20mA Transducer = Sensor Low Range Value -

Gain

Example: Temperature sensor with a sensing range of 50-95°F -

displayed in Fahrenheit

Gain = (95-50) / 4 = 11.25 | Offset = 50 - 11 = 38.75
Example: Temperature sensor with a sensing range of 50-95°F -

displayed in Celsius

Convert 50-95°F to 10-35°C and use the Celsius range for the

calculations

Gain = (35-10) / 4 = 6.25 | Offset = 10 - 6 = 3.75
Example: Humidity sensor with a range of 0 - 100% RH

Gain = (100-0) / 4 = 25 | Offset = 0 - 25 = -25

Gain for 0-5V or 0-10V Transducer = Sensor High Range Value-

Sensor Low Range Value

Offset for 0-5V or 0-10V Transducer = Sensor Low Range Value

Example: A 0-5V Transducer with a range of -30-175°F

Gain = 175 - -30 = 205 | Offset = -30
Example: A 0-5V Transducer with a range of 0 - 100%RH

Gain = 100 - 0 = 100 | Offset = 0

Option

Description

Table 3.3

FMS Main Board Configuration Options

Advertising