2 eia-485, Eia-485, Figure 4.3 – RLE FMS V.1.13 User Manual

Page 136: Eia-485 wiring connections, Table 4.2, Com1 tb5 pin out

Advertising
background image

136

FMS User Guide

970.484.6510

4

Advanced Communications - Modbus, BACnet, and Telnet

4.2.2 EIA-485

The EIA-485 COM Port 1 on the FMS is used to connect the FMS-as a Modbus Master-to one

or more Modbus Slave devices or it is used to connect a Modbus Master device to the FMS as

a Modbus Slave. The Modbus EIA-485 is active over COM1 (TB5 Pins 8, 9 and 10). The EIA-

485 port allows communications between one Modbus Master and one or more Modbus Slave

devices. EIA-485 can accommodate up to 4,000 feet (1,219m) of cable length. There are many

variations on how terminals are labeled on EIA-485 2-wire (e.g., some devices use (+) and (-)

or A and B, and some use (-) and (+) or B and A. Therefore, if a Slave unit is not responding,

try swapping the wires.

Figure 4.3

EIA-485 Wiring Connections

Pin

Description

8

EIA-485(+)

9

EIA-485(-)

10

Ground

Table 4.2

COM1 TB5 Pin Out