Advanced Communications - Modbus, BACnet, and Telnet

Register Acquisition Designate how the register should be acquired.

Register/Offset

Enter the Register Number for the data to be read. The Register

Number is located on the Slave Units Register Map; see

4.7.1,

“Slave Register Map” on page 155

.

Register Type

Select the Data Type of the Register.

Unsigned Int

Signed Int

Long

Float

Alarm Bit/ ON= ALARM

Alarm Bit/ OFF=ALARM

Status Bit - No Log

Status Bit - Logged

Coil Status

Input Status

NOTE: Refer to the manufacturer’s equipment guide for the register

numbers and the data type.

Scaler

Select a multiplier for the data value.

Custom Gain

If you’d like a gain to be applied to the value, designate that here.

Offset

Allows users to fine-tune analog values. Offset adjustment may be

required by certain manufacturers.

Bitflag

Applies to Data Types, Alarm Bit, Status Bit-Logged and Status Bit -

No Log. Selects which bit is read from the 16 or 32 bit register

value.

Registers

Designate the correct type of read holding/input register.

Word Order

Applies to Data Types Long and Float. Long and Float Data Types

read two consecutive registers. The word order selects if the first

register is the larger or smaller part of the number.

Label

Enter a label to describe the Data Point.

UOM/Map Label

Specify the unit of measure you are using for this specific point.

Log Index

Applies to Data Types Signed Int, Unsigned Int, Long and Float.

The FMS has 232 entries reserved for logging (Min, Hour and Day

Logs). Enter a value of 1 to 232 if the point is to be internally logged

on the FMS. Each register to be logged requires a unique entry

number.

UOM Conversion

Convert a unit of measure from the way it is communicated by the

device to the way you would like to have it displayed.

deg C - deg F (1,10,100,1000 Scale)

deg C - deg F (1/32 Scale

kPa - PSI (1/8, 1/28 Scale)

Enumerated Label

Set

Sets of enumerated labels can be configured from the Enumerated

Labels Configuration link on the bottom of the Modbus/Snmp/

Bacnet Slave units page. If you have a label set configured,

designate which one you’d like to use here.

Option

Description

Table 4.6

Individual Modbus Register Configuration Options