Advanced Communications - Modbus, BACnet, and Telnet

Object Type

Select the appropriate object type:

Analog Input

Analog Output

Analog Value

Binary Input

Binary Output

Binary Value

Multistate Value

Instance-PV

Designate the appropriate instance-pv.

Binary Alarm

Check this box if the register is a binary alarm.

Label

Enter a label to describe the Data Point.

UOM/Map Label

Specify the unit of measure you are using for this specific point.

Log Index

Applies to Data Types Signed Int, Unsigned Int, Long and Float.

The FMS has 232 entries reserved for logging (Min, Hour and Day

Logs). Enter a value of 1 to 232 if the point is to be internally logged

on the FMS. Each register to be logged requires a unique entry

number.

Enumerated Label

Set

Sets of enumerated labels can be configured from the Enumerated

Labels Configuration link on the bottom of the Modbus/Snmp/

Bacnet Slave units page. If you have a label set configured,

designate which one you’d like to use here.

Analog Alarm Type

Designate which type of analog alarm this will be.

Alarm Thresholds:

High 2, High1, Low1,

Low2

Set high and low - or major and minor - thresholds for alarm analog

alarm values being read by these points.

Multistate Active

Value

If you’d like to designate an multistate active value, do so here.

Snmp Trap

Recipients

The SNMP/Syslog page allows you to configure SNMP trap

recipients. Once those are configured, you can designate which IP

addresses should receive traps for this register.

Map Box Size

Customize the size of the mapped object. By default, the height of

the object, as it appears on the map, is approximately 20 pixels,

and the width automatically adjusts to the length of the text. This

setting allows users to expand the size of the object to fill a defined

area.

Map Coordinate

Fine tune the location of the object on the map. Refer to

“Map

(Facility Mapping)” on page 114

for further information.

Graphical Mapping

Designate the device’s location on the FMS graphical map. Refer to

“Map (Facility Mapping)” on page 114

for further information.

Test Map

View the mapped location of the point you’re currently configuring.

Option

Description

Table 4.8

Individual Bacnet Register Configuration Options