Title: Fault Declarations

The information contained in this document is the

CONFIDENTIAL

property of

MagneTek Inc.

File = N:\PROJECT\515\SmartTrac\DOCS\Faults.DOC

Print Date: 10/17/00

19

Displayed Fault No.

Priority

D

is

p

lay?

Newest

List

?

Ol
d

es

t

List

?

Severity

Assig

n

Program

Input

Corrective Action

Control

Node

Monitor

Fault

Manager

Fault Legend

Description

7FFE

32766

Watchdog
Timeout

One or more Program Units
associated with a Task have not
been completed within the
‘Watch Dog Timeout’ setting.

Yes

Yes

Yes

Critical

Critical

and

Major

Extend the Watchdog Timeout for the faulted
Task. Generally, do not exceed 3x the cyclic
task’s value nor 300ms for an IoSync Task.
Application program may be overburdened –
reduce amount of logic placed in fast Tasks
(15ms or faster) to slow Tasks (30ms or slower).
This may include reducing number of Program
Units and/or program elements.

7FFF

32767

Fatal Error

Unrecoverable fault, usually
occurs during Driver startup.

Yes

Yes

Yes

Critical

Critical

and

Major

Verify that there are no hardware problems on
the PC used to create the application. Re-
compile and reload the program and reload it to
the SmartTrac drive. The Smart Trac main CPU
card may be faulty. If available, download a
small test program to see if fault persists.