31

Displayed Fault

No.

Priority

D

is

p

lay?

Newest

List

?

Ol
d

es

t

List

?

Severity

Assig

n

Program

Input

Corrective Action

Control

Node

Monitor

Fault

Manager

In

ternal Fault #

Fault Legend

Description

14E24

85540

20004

DPRAM Address

DPRAM bad address or
register requested fault
between the Smart Trac AC1
CPU card and the inverter
control card.

Yes

Yes

Yes

Minor

Major

Check for correct inverter model number;
don’t forget to initialize the inverter card if
model number was changed. Make sure the
inverter Control Method is set to ‘Flux
Vector’ (typical).

14E25

85541

20005

DPRAM Param
Num

Bad number of parameters
requested from Dual Port
RAM of the Smart Trac AC1
CPU card (to inverter control
card).

Yes

Yes

Yes

Minor

Major

The Smart Trac main CPU card may be
faulty. If available, download a small test
program to see if fault persists.

14E26

85542

20006

DPRAM Parm
Range

Bad parameter data specified
between the Smart Trac AC1
CPU card and the inverter
control card. Parameter
setting sent to inverter is out
of range for that inverter.

No

Yes

Yes

Minor

Minor

Check for correct inverter model number;
don’t forget to initialize the inverter card if
model number was changed. Look for
obvious mistakes in the application
program such as attempting to alter
inverter current settings. Make sure the
inverter Control Method is set to ‘Flux
Vector’ (typical).

14E27

85543

20007

DPRAM Chg @
Run

Dual Port RAM non-run
inverter parameter change
requested between the Smart
Trac AC1 CPU card and the
inverter control card while
the inverter is running.

No

Yes

Yes

Minor

Minor

Certain parameters cannot be changed
while the inverter is running a motor.
Application program should be structured
to avoid writes to these parameters during
Run conditions.