6. Inverter

The following section details fault numbers assigned to the Smart Trac AC1 Inverter (Power Conversion Unit).

Notes:

Inverter faults will be declared only if properly setup in Fault Manager, DPRAM Interface Card, and the application program.

These faults are declared when the inverter sees them as major faults. As Minor faults, these fault codes are not generated but drive may still set a minor fault bit.

All Inverter faults listed here correspond to those found in MagneTek’s GPD515 Technical Manual.

Displayed Fault

No.

Priority

D

is

p

lay?

Newest

List

?

Ol
d

es

t

List

?

Severity

Assig

n

Program

Input

Corrective Action

Control

Node

Monitor

Fault

Manager

In

ternal Fault

No
.

Fault Legend

Description

17530

95536

30000

DC Bus Fuse Open

PUF – Fuse blown. DC fuse has
cleared.

Yes

Yes

Yes

Minor

Major

Check for short circuit in output
circuitry. Possibility of motor
windings T1, T2 and/or T3 shorted.
Possibility of drive output phases
shorted to ground. Possibility power
transistors are damaged.

17531

95537

30001

DC Bus Undervolt

UV1 – Main circuit undervoltage.
Occurs 2 seconds after detection of
low voltage. Detection levels:
190VDC for 230V rated unit;
380VDC for 460V rated unit;
546VDC for 600V rated unit.

Yes

Yes

Yes

Minor

Major

Check input AC supply. Possibility
of erroneous operation due to noise:
remove noise source by connecting
surge suppressor to relay and
magnetic contactor coils; provide line
filter to remove noise on input power
line. Possibility of gate drive PCB is
faulty. Note: fault is declared only if
drive is in Run mode.

17532

95538

30002

CTL PS Undervolt

UV2 – Control circuit undervoltage.
Control circuit voltage is low during
operation.

Yes

Yes

Yes

Minor

Major

Possibility of poor DC supply being
furnished by drive. Note: fault is
declared only if drive is in Run
mode.