40

Displayed Fault

No.

Priority

D

is

p

lay?

Newest

List

?

Ol
d

es

t

List

?

Severity

Assig

n

Program

Input

Corrective Action

Control

Node

Monitor

Fault

Manager

In

ternal Fault

No
.

Fault Legend

Description

17537

95543

30007

DC Bus Overvolt

OV – Overvoltage. Detection levels:
400VDC for 230V rated unit;
800VDC for 460V rated unit;
1050VDC for 600V rated unit.

Yes

Yes

Yes

Minor

Major

Check input AC supply. Possibility
of erroneous operation due to noise:
remove noise source by connecting
surge suppressor to relay and
magnetic contactor coils; provide line
filter to remove noise on input power
line. If OV trip occurs during
deceleration, increase deceleration
time; may need dynamic braking
option. Note: fault is declared only if
drive is in Run mode.

17538

95544

30008

Heatsnk Overtemp

OH – Cooling fin overheat.
Heatsink fin temperature exceeded
preset value found in inverter
parameter L8-02.

Yes

Yes

Yes

Minor

Minor

Major fault declared only if inverter
parameter L8-03

3. Reduce

ambient temperature to less than
45˚C (113˚ F). Clean heat sink.
Replace cooling fan if necessary.

17539

95545

30009

Heatsnk MAX
Temp

OH1 – Drive overheat. Heatsink fin
temperature exceeded 105˚ C (221˚
F).

Yes

Yes

Yes

Minor

Major

Reduce ambient temperature to less
than 45˚C (113˚ F). Clean heat sink.
Replace cooling fan if necessary.