Title: Fault Declarations

The information contained in this document is the

CONFIDENTIAL

property of

MagneTek Inc.

File = N:\PROJECT\515\SmartTrac\DOCS\Faults.DOC

Print Date: 10/17/00

54

Displayed Fault

No.

Priority

D

is

p

lay?

Newest

List

?

Ol
d

es

t

List

?

Severity

Assig

n

Program

Input

Corrective Action

Control

Node

Monitor

Fault

Manager

In

ternal Fault

No
.

Fault Legend

Description

175F9

95737

30201

Alm:DC Bs Ovrvlt

OV – Overvoltage. Detection levels:
400VDC for 230V rated unit;
800VDC for 460V rated unit;
1050VDC for 600V rated unit.

Yes

Yes

Yes

Minor

Minor

Check input AC supply. Possibility
of erroneous operation due to noise:
remove noise source by connecting
surge suppressor to relay and
magnetic contactor coils; provide line
filter to remove noise on input power
line. Note: The input labeled ‘Minor’
is declared only if drive is NOT in
Run mode and only if this is
programmed as an ALARM.

175FA

95738

30202

Alm:Htsnk Ovrtmp

OH – Cooling fin overheat.
Heatsink fin temperature exceeded
preset value found in inverter
parameter L8-02.

Yes

Yes

Yes

Minor

Minor

Alarm declared only if inverter
parameter L8-03 = 3. Reduce
ambient temperature to less than
45˚C (113˚ F). Clean heat sink.
Replace cooling fan if necessary.

175FB

95739

30203

Alm: Over Heat 2

OH2 – External detection of
heatsink overtemp. One of H1-01
through H1-06 is programmed for
this alarm and that terminal input is
closed.

Yes

Yes

Yes

Minor

Minor

Reduce ambient temperature to less
than 45˚C (113˚ F). Clean heat sink.
Replace cooling fan if necessary

175FC

95740

30204

Alm:Ovrtrq Det 1

OL3 – Overtorque detect 1 alarm.
Output torque exceeded the
Overtorque Detection Level 1 set in
L6-02 for vector control.

Yes

Yes

Yes

Minor

Minor

The input labeled ‘Minor’ is set only
if L6-01 = 1 or 2. Reduce load,
increase acceleration time, or
increase inverter parameter setting
L6-02.