Title: Fault Declarations

The information contained in this document is the

CONFIDENTIAL

property of

MagneTek Inc.

File = N:\PROJECT\515\SmartTrac\DOCS\Faults.DOC

Print Date: 10/17/00

49

Displayed Fault

No.

Priority

D

is

p

lay?

Newest

List

?

Ol
d

es

t

List

?

Severity

Assig

n

Program

Input

Corrective Action

Control

Node

Monitor

Fault

Manager

In

ternal Fault

No
.

Fault Legend

Description

value outside the permitted
range.

03- Terminal. Multi-function input

setting fault.

05- Sequence Select. Option card

selection fault.

06- PG Opt Missing. PG card not

installed.

07- Analog Selection. Multi-

function analog input selection
fault.

08- Terminal. Selection parameter

fault. A parameter has been
changed that is not available in
the present control method.

10- V/F Ptrn Setting. V/f data

setting fault.

11- CarrFrq/ON-Delay. Carrier

frequency parameter(s) set out
of range.

source is set for option card
(Smart Trac.AC1 CPU card) i.e.
B1-01, B1-02 = 3, but no option
card is connected.

06- Control method set to flux vector

or V/F with PG, and no PG card
is installed.

07- Both multi-function analog

inputs on the inverter card, H3-
05 and H3-09, have been
programmed for the same data
(except 1F).

08- May be trying to change an

inverter parameter that is not
available in closed loop vector
mode.

10- Occurs when the custom V/f

pattern does not meet the
following criteria: inverter
parameters E1-04 > E1-06 > E1-
07 > E1-09.

11- Occurs when the carrier

frequency inverter parameters
are set as follows: C6-01 > 5
kHz and C6-02 < 5 kHz; C6-03
> 6 and C6-01 < C6-02.

17561

95585

30049

Not used