10/17/00

New Berlin

Technology Center

Smart Trac

Product

Development

Design

Document

Faults.doc

Rev. # 19

Page 44 of 64

Title: Fault Declarations

The information contained in this document is the

CONFIDENTIAL

property of

MagneTek Inc.

File = N:\PROJECT\515\SmartTrac\DOCS\Faults.DOC

Print Date: 10/17/00

44

Displayed Fault

No.

Priority

D

is

p

lay?

Newest

List

?

Ol
d

es

t

List

?

Severity

Assig

n

Program

Input

Corrective Action

Control

Node

Monitor

Fault

Manager

In

ternal Fault

No
.

Fault Legend

Description

17547

95559

30023

Overspeed

OS – Motor overspeed. Motor speed
exceeded overpspeed level set by
inverter parameters F1-08, F1-09.

Yes

Yes

Yes

Minor

Major

Check for correct tach (encoder) PPR
value in inverter parameter F1-01.
May have excessive noise on encoder
signal inputs to Smart Trac AC1
drive. Consult MagneTek about
specifications of user-supplied
encoder. Major fault declared only if
inverter parameter F1-03

3, else a

minor fault.

17548

95560

30024

Speed Deviation

DEV – Speed deviation. Difference
between speed reference and speed
feedback exceeded the deviation
level set in inverter parameters F1-
10, F1-11.

Yes

Yes

Yes

Minor

Major

Decrease load, increase
acceleration/deceleration times, or
increase deviation levels found at
inverter parameters F1-10, F1-11.
The input labeled ‘Major’ will be set
only if inverter parameters A1-02 = 1
or 3, and d5-01 = 0, and F1-04

3.

17549

95561

30025

PG Open

PGO – PG cable wires are
disconnected, bad tach, tach is not
connected to motor, or missing tach
power supply. This is actually a
tach loss condition.

Yes

Yes

Yes

Minor

Major

Connect wires from the Smart Trac
AC1 PG card to encoder, or look for
damaged wires. The input labeled
‘Major’ will be set only if inverter
parameters A1-02 = 1 or 3, and d5-01
= 0, and F1-02

3.

1754A

95562

30026

Input Pha Loss

PF – Inverter input phase missing.
Incoming power supply has an open
phase, or a large imbalance exists
between L1, L2, and L3.

Yes

Yes

Yes

Minor

Major

Check input AC supply. Note:
inverter parameter L8-05 = 1 enables
this fault.

Advertising