Product

Development

Design

Document

Faults.doc

Rev. # 19

Page 43 of 64

Title: Fault Declarations

The information contained in this document is the

CONFIDENTIAL

property of

MagneTek Inc.

File = N:\PROJECT\515\SmartTrac\DOCS\Faults.DOC

Print Date: 10/17/00

43

Displayed Fault

No.

Priority

D

is

p

lay?

Newest

List

?

Ol
d

es

t

List

?

Severity

Assig

n

Program

Input

Corrective Action

Control

Node

Monitor

Fault

Manager

In

ternal Fault

No
.

Fault Legend

Description

17543

95555

30019

External Fault 6

EF6 – External fault signal at
terminal 6 of the inverter card. This
can be programmed to be N.O. or
N.C. contact.

Yes

Yes

Yes

Minor

Major

A fault has occurred in circuits
outside the Smart Trac AC1 inverter
card. Troubleshoot and correct. The
input labeled ‘Major’ will be true
only if inverter parameter H1-04 = 20
to 2B hex.

17544

95556

30020

External Fault 7

EF7 – External fault signal at
terminal 7 of the inverter card. This
can be programmed to be N.O. or
N.C. contact.

Yes

Yes

Yes

Minor

Major

A fault has occurred in circuits
outside the Smart Trac AC1 inverter
card. Troubleshoot and correct. The
input labeled ‘Major’ will be true
only if inverter parameter H1-05 = 20
to 2B hex.

17545

95557

30021

External Fault 8

EF8 – External fault signal at
terminal 8 of the inverter card. This
can be programmed to be N.O. or
N.C. contact.

Yes

Yes

Yes

Minor

Major

A fault has occurred in circuits
outside the Smart Trac AC1 inverter
card. Troubleshoot and correct. The
input labeled ‘Major’ will be true
only if inverter parameter H1-06 = 20
to 2B hex.

17546

95558

30022

Not used