Title: Fault Declarations

The information contained in this document is the

CONFIDENTIAL

property of

MagneTek Inc.

File = N:\PROJECT\515\SmartTrac\DOCS\Faults.DOC

Print Date: 10/17/00

47

Displayed Fault

No.

Priority

D

is

p

lay?

Newest

List

?

Ol
d

es

t

List

?

Severity

Assig

n

Program

Input

Corrective Action

Control

Node

Monitor

Fault

Manager

In

ternal Fault

No
.

Fault Legend

Description

1755E

95582

30046

Not used

1755F

95583

30047

CPFxx Hardwr Flt

This corresponds to a series of
Smart Trac AC1 inverter faults of
type CPFxx where ‘xx’ stands for
the number of the fault as listed
below:
00- COM-ERR (OP&INV). Control

circuit fault 1. Communication
between Digital Operator and
Smart Trac AC1 was not
established within 5 seconds
after power was applied, or an
internal hardware or software
fault was detected on power-up.

01- COM-ERR (OP&INV). Control

circuit fault 2. Communication
between Digital Operator and
Smart Trac AC1 has not
occurred within 2 seconds after
the last communication, or an
internal hardware or software
fault was detected after power-
up.

02- BB Circuit Failure. Baseblock

circuit fault.

03- EEPROM Error. EEPROM

fault.

Yes

Yes

Yes

Minor

Major

00- Possibility boot code does not

exist in Smart Trac AC1 CPU
card. Check integrity of cable
between digital operator and
Smart Trac AC1.

01- Operating system on Smart Trac

AC1 CPU card may have
stopped running. Application
program may be invalid. Check
integrity of cable between digital
operator and Smart Trac AC1.

02- Major faults like overspeed or

max overheat of drive will cause
inverter baseblock of signals to
power devices. Recycle Smart
Trac AC1 power. If problem
persists, replace inverter card.

03- Attempt to initialize Smart Trac

AC1 inverter card. Replace
inverter card if failure persists

04- Replace inverter card.
05- Replace inverter card.
06- Check physical connection of

both Smart Trac AC1 CPU card
and PG card to inverter card.

21- Smart Trac AC1 CPU card may

Advertising