Title: Fault Declarations

The information contained in this document is the

CONFIDENTIAL

property of

MagneTek Inc.

File = N:\PROJECT\515\SmartTrac\DOCS\Faults.DOC

Print Date: 10/17/00

58

Displayed Fault

No.

Priority

D

is

p

lay?

Newest

List

?

Ol
d

es

t

List

?

Severity

Assig

n

Program

Input

Corrective Action

Control

Node

Monitor

Fault

Manager

In

ternal Fault

No
.

Fault Legend

Description

1760B

95755

30219

Alm:Memobus
Comm

CE – Communication fault. Control
data was not received for 2 seconds
after initial communication.

Yes

Yes

Yes

Minor

Minor

This is a serial communications error.
If h5-05=1, then the alarm bit will be
set if no serial communication is seen
AND h5-04= 3. Check validity of
Smart Trac AC1 CPU card firmware
and application program.

1760C

95756

30220

Alm:Mtr Overlded

OL1 – Motor overload. Protects the
motor. Motor thermal overload
protection has tripped. Inverter
parameter L1-02 has been exceeded
(initial value: 150% for 60 sec.).

Yes

Yes

Yes

Minor

Minor

Alarm is declared if thermal overload
exceeds 90% of fault detection level
AND L1-01= 1. Load may be too
large. Check drive capacity (inverter
parameter o2-04) for correct factory
setting. Check for proper setting of
electronic thermal overload setting:
inverter parameters E1-02, E2-01,
L1-02. Try disconnecting motor
wiring from output terminals – if OL
is still indicated, problem may be due
to noise or faulty inverter cards

1760D

95757

30221

Alm:Inv Overlded

OL2 – Drive overload. Protects the
Smart Trac AC1 drive. Drive
overload protection has tripped.

Yes

Yes

Yes

Minor

Minor

See fault “Motor Overloaded” for
details.