ProSoft Technology MVI56-103M User Manual

Page 101

Advertising
background image

MVI56-103M ♦ ControlLogix Platform

Reference

IEC 60870-5-103 Master Communication Module

User Manual

ProSoft Technology, Inc.

Page 101 of 152

February 22, 2013

As blocks are transferred between the module and the processor, each block
contains block identification codes that define the content or function of the block
of data transferred. The block identification codes used by the module are
displayed in the following table.

Block Range

Descriptions

-1

Null block

0

Null block

1 to 20

Read or write data

9901

User Constructed Command

9902

Command Control Block (Add command to Command List Queue)

9903

Event Messages from Master port

9950

Command List Error data

9970

Set PLC time using module's time

9971

Set module's time using ControlLogix time

9998

Warm Boot Request from ControlLogix (Block contains no data)

9999

Cold Boot Request from ControlLogix (Block contains no data)

Blocks -1 and 0 transfer status data from the module to the processor and they
contain no data when transferred from the processor to the module. Blocks 1 to
20 are utilized to transfer data stored or to be stored in the module's database.
These data blocks send data from module to the processor (monitored data
received from the devices on the serial network) and to send data from the
processor to the module (control data to send to the end devices). Block
identification codes 9901 to 9999 are used for special control blocks to control
the module.