Iec-870-5-103 master port x – ProSoft Technology MVI56-103M User Manual

Page 37

Advertising
background image

MVI56-103M ♦ ControlLogix Platform

Configuring the MVI56-103M Module

IEC 60870-5-103 Master Communication Module

User Manual

ProSoft Technology, Inc.

Page 37 of 152

February 22, 2013

2.5

[IEC-870-5-103 Master Port x]

These section configures the communication parameters for each application
serial port on the module. The following illustration shows typical settings for a
Master port.

[IEC-870-5-103 Master Port 0]
Baud Rate : 19200
Parity : Even
RTS On : 0
RTS Off : 1
Minimum Delay : 10
Receive Timeout : 2000
Single char ACK F0,1 or 3 : Yes

2.5.1 Baud Rate

This is the baud rate to be used on the port. Enter the baud rate as a value. For
example, to select 19K baud, enter 19200.

Baud Rate

Parameter Value Options

110

110

150

150

300

300

600

600

1200

12 or 1200

2400

24 or 2400

4800

48 or 4800

9600

96 or 9600

19,200

19, 192 or 19200

38,400

38, 384 or 38400

57,600

57 or 576

115,200

115 or 1152

2.5.2 Parity

N, O, E, M, or S

This parameter sets the parity to be used on the port. The values correspond to
the following settings: N=None, O=Odd, E=Even, M=Mark and S=Space.

Note: The 103M specification supports only Even Parity.

2.5.3 RTS On

0 to 65535

milliseconds

This parameter sets the number of milliseconds to delay after Ready To Send
(RTS) is asserted before data will be transmitted.